South Korea drafts cooling and power-design criteria for AI data centers
South Korea's Ministry of Science and ICT has opened a public consultation on draft implementing rules for the AI Data Center Special Act. The proposals set cooling design criteria tied to AI equipment parameters and cap a facility design-power ratio at 1.5 relative to IT load.

The draft decree, published for public comment on 20 November 2026, prescribes how cooling systems in AI data centers must be designed. Under proposed Article 3, cooling capacity must be sufficient to maintain the temperature, humidity, coolant temperature, and flow conditions specified by the AI equipment's designers, manufacturers, or suppliers. Where the identity of future tenant equipment cannot yet be determined, the cooling design capacity would instead be assessed against the heat generated by the facility's AI racks.
On the power side, the draft requires that uninterruptible and emergency power provisions cover both cooling and IT equipment. A proposed design-power ratio — total designed facility power divided by designed IT equipment power — would be subject to a ministerial threshold no higher than 1.5. The text clarifies that this ratio is a design parameter, not a measured annual PUE.
The consultation closes on 30 December 2026. The AI Data Center Special Act itself is scheduled to take effect on 10 March 2027. All figures and thresholds described above are consultation proposals and are not requirements in force.