Standards & safety
Xingguo County Report Details Residual HF Acid Injury During R22 Workshop Vessel Removal
A Xingguo County investigation into a March incident at an R22 production workshop found that a contractor was injured by residual low-concentration hydrofluoric acid when a buffer vessel was tilted during removal. The report cites missing acid-resistant PPE, inadequate task-specific training, and weak supervision of protective measures as contributing factors.

A maintenance-safety investigation published by Xingguo County on 12 October 2026 identifies a cluster of preventable failures behind a contractor injury at an R22 production workshop. The report, covering a 14 March incident, classifies the event as a minor-injury accident under its stated criteria while noting that the chemical exposure was not harmless.
What the investigation found
Investigators determined that the contractor was injured by residual low-concentration hydrofluoric acid that escaped when a buffer vessel was tilted during its removal. Before the operation, staff had opened the vessel's bottom drain and observed no liquid, leading them to assume no residual acid remained. The acid was released only when the vessel changed orientation.
The report lists four contributing factors:
- Absence of acid-resistant clothing for the task.
- Protective gloves had been removed before the vessel was handled.
- Task-specific training on residual-acid hazards was inadequate.
- Supervision of protective measures during the removal was weak.
Context and scope
The case is a retrospective maintenance-safety review of a production-workshop incident, not a report of a new accident or a refrigerant leak in ordinary air-conditioning service. The classification as a minor-injury accident reflects the county's stated criteria and does not imply that the hydrofluoric-acid exposure carried no health risk.
ORIGINAL SOURCE
制冷快报 ↗Visit the original source for additional details.